Data format for ModBusEasy sendings in HTTP (manual)
 
The format is identical to that of MBusEasy. 
 
With the ModBus Reading/Settings menu, you can enter the URL of your own script (must be standard http:// and for the default port, 80); either as http://www.aserver.com/nicescript.php or simply www.aserver.com/nicescript.php
Or nicescript.pl or nicescript.py - any server programming language that can read a POST request in normal CGI standard is OK; the name of the script is your choice. 
 
The CGI parameters passed on are: 
webid (unique identifier; preset when ModBusEasy is assembled) 
rmt (remote mode: WiFi or gsm; you may use it for display purpose) 
batt (battery charge in % - if less than 25 batteries must be replaced) 
rtim (current reading frequency in minutes) 
rtimset (if this is 1, a end user has just changed the reading frequency, locally) 
err (errors, if any, in plain text) 
f (the readings, in plain text as HEX to Ascii) 
 
The server MUST reply with a short text reply (any reply will be actually read as text; lines terminated by LF), in this format: 
This is a message (one line) that will be shown to the end user if present. 
OK data saved 
2019-03-31 10:11 (the current UTC/GMT time, used to adjust the internal Clock) 
2019-03-31 10:11 (last reading time; or can be a empty line) 
2019-03-31 10:11 (last correct reading time; or can be a empty line) 
360 (reading frequency for next reading, in minutes) 
(empty line) 
(empty line) 
0 (summer mode) 
(empty line) 
(empty line) 
(empty line) 
(empty line) 
(empty line) 
(empty line) 
END 
 
 
ModBusEasy 
 
 
Here are the quick manuals for some other products: 
- connection and control manual, WiFi HTTP and MQTT for DoorOpen/DoorSwitch 
- connection and control manual, WiFi HTTP and MQTT for QueueNumber and MultiQueue 
- connection and control manual, WiFi HTTP and MQTT for Orologio/SuperClock 
- connection and control manual, WiFi HTTP and MQTT for TXtemp, TXdata, TXsoil 
 
- connection and control manual, Serial RS232 for 8888-Display (ModBus WiFi HTTP MQTT) 
- connection and control manual, ModBus for 8888-Display (RS485 ModBus WiFi HTTP MQTT) 
- connection and control manual, WiFi/HTTP for 8888-Display (ModBus WiFi HTTP MQTT) 
- connection and control manual, WiFi/MQTT for 8888-Display (ModBus WiFi HTTP MQTT) 
 
- manual with data format for data sent by HTTP for RXTXeasy 